DM 2000B / DM 1000B

Rydair ( MERV 14 Modular Electronic Air Cleaner )

The Rydair Modular Electronic Air Cleaner (EAC) is a commercial unit designed for use in Custom Air Handling Units (AHUs). It reduces the amount of airborne particulates from soiling the AHU's cooling coils in mechanical pre and post filters. As a result of lower pressure drop of the EAC compared to conventional mechanical filters, huge savings in energy consumption is made possible.

Specifications

DM 2000B
unit :

Dimensions (HxWxL) : 682 x 615 x 200 mm

Weight : 26 kg

Cabinet : Galvanized Steel, 1.2 mm Hot Dip

Power / Ratings :

Operating Voltage : 220/230 VAC, 50/60 Hz

Power Consumption : 36 Watts

Ionising Voltage : 8.1 KVdc

Collector Voltage : 4.1 KVdc

Air Flow :

Max Air Volume : 3400 CMH

Pressure Drop : 0.11" WG to 0.25" WG (28 Pa to 66 Pa)

Efficiency :

Particle Size : 0.01 microns - 10 microns

MERV Ratings : Meets MERV 14

ASHRAE 52.2-2012 : up to 96% single pass, up to 99% double pass

Operating temperature : 4°C to 55°C

Electrostatic Cell :

Dimensions (HxWxL) : 505 x 315 x 200 mm

No. of Cells / Weight : 2 / 7 kg each

No. of Plates per cell : 75

No. of Ionizing wires per cell : 9

Material : Aluminum

DM 1000B
unit :

Dimensions (HxWxL) : 367 x 615 x 200 mm

Weight : 17 kg

Cabinet : Galvanized Steel, 1.2 mm Hot Dip

Power / Ratings :

Operating Voltage : 220/230 VAC, 50/60 Hz

Power Consumption : 30 Watts

Ionising Voltage : 8.1 KVdc

Collector Voltage : 4.1 KVdc

Air Flow :

Max Air Volume : 1700 CMH

Pressure Drop : 0.11" WG to 0.25" WG (28 Pa to 66 Pa)

Efficiency :

Particle Size : 0.01 microns - 10 microns

MERV Ratings : Meets MERV 14

ASHRAE 52.2-2012 : up to 96% single pass, up to 99% double pass

Operating temperature : 4°C to 55°C

Electrostatic Cell :

Dimensions (HxWxL) : 505 x 315 x 200 mm

No. of Cells / Weight : 1 / 7 kg each

No. of Plates per cell : 75

No. of Ionizing wires per cell : 9

Material : Aluminum

Features

Short circuit, arc protection and auto restore power supply

BMS (Building Management System) terminals provided

Auto power cut-off when door is opened

Indicator LEDs for normal or wash indicator

Set of terminals for remote LED normal or wash indicator

Charcoal post filter for odour reduction option

Front Loading Cell

Mounting / Installation

Air return of AHU/Fresh air inlet

Related product