Plasma Air - model 50f

The Model 50F can be installed in metal duct utilizing the factory supplied gaskets and pre-drilled flange. The contractor makes a duct cut out and secures the unit with self tapping sheet metal screws. The unit can also be installed inside an HVAC unit utilizing a contractor supplied mounting bracket. Power to the unit should be interlocked with system fan operation. The power input fitting permits easy disconnection of the power supply for unit service. A five position ion level switch varies the ion output between 50% and 100%. A low voltage connection and a five foot cable are provided for remote monitoring of unit operation.

SPECIFICATIONS

Airflow Capacity: ......... Up to 10,000 CFM

Pressure Drop: ......... See Figure 1

Housing Material: . . . . . . . . . . . . . . . . 22 gauge steel

Weight: ......... 18 pounds

Maximum Operating Temperature: 200º F (93º C)

Electrical:

Voltage: ......... 115V (51F)/230V (52F)

Power Consumption: ......... 50 watts

Current Draw: ......... 0.3A (51F)/0.15A (52F)

Frequency: ......... 50/60 hertz

Internal Fuse: ......... 1.0 amp

Field Electrical Connection: ......... 3/8”flexiblemetal conduit (BX)

Ionization Tube:

Material: ......... Glass, stainless steel

Number of Tubes: ......... Five (5)

Size: ......... F

Length: ......... 21 inches

Life: ......... 8,800 hours

Related product